Setting Guidelines - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
4.2.6.2
Application manual

Setting guidelines

Redundant communication (DUODRV) is configured in the local HMI under Main
menu/Settings/General settings/Communication/Ethernet configuration/Rear
OEM - Redundant PRP
The settings can then be viewed, but not set, in the Parameter Setting tool in PCM600
under Main menu/IED Configuration/Communication/Ethernet configuration/
DUODRV:
Operation: The redundant communication will be activated when this parameter is set
to On.After confirmation the IED will restart and the setting alternatives Rear OEM -
Port AB and CD will not be further displayed in the local HMI. The ETHLANAB and
ETHLANCD in the Parameter Setting Tool are irrelevant when the redundant
communication is activated, only DUODRV IPAdress and IPMask are valid.
Section 4
Station communication
815