Setting Parameters; Pole Slip Protection Pspppam (78); Application - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
3.6.12.3
Table 80:
ZMRPSL Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tDZ
0.000 - 60.000
tDZMUR
0.000 - 60.000
tCS
0.000 - 60.000
tTrip
0.000 - 60.000
tBlkTr
0.000 - 60.000
3.6.13
3.6.13.1
374
of the faults on adjacent power lines. It is necessary to consider the possibility for the
faults to occur close to the set reach of the underreaching distance protection zone,
which might result in prolonged operate times of zone 1 (underreaching zone)
compared to zone 2 pickuped time (overreaching zone). A setting between 80 and 150
ms is generally sufficient.
The release timer tZL permits unconditional operation of the underreaching zone, if the
measured impedance remains within its operate characteristic longer than the set time
tZL. Its setting depends on the expected speed of the initial swings and on the setting of
the time delay for the overreaching zone 2. The release timer must still permit selective
tripping of the distance protection within the complete network. A setting between 200
and 300 ms is generally sufficient.

Setting parameters

Unit
Step
-
-
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001

Pole slip protection PSPPPAM (78)

Function description
Pole slip protection

Application

Normally, the generator operates synchronously with the power system, that is, all the
generators in the system have the same angular velocity and approximately the same
phase angle difference. If the phase angle between the generators gets too large the
stable operation of the system cannot be maintained. In such a case the generator loses
the synchronism (pole slip) to the external power system.
Default
Description
Disabled
Disable/Enable Operation
0.050
Permitted max oper time diff between higher
and lower zone
0.200
Delay for oper of underreach zone with
detected diff in oper time
0.100
Conditional timer for sending the CS at power
swings
0.100
Conditional timer for tripping at power swings
0.300
Timer for blocking the overreaching zones trip
IEC 61850
IEC 60617
identification
identification
PSPPPAM
1MRK504116-UUS C
ANSI/IEEE C37.2
device number
U
78
cos
Application manual