For switches with an individual operation gear per phase, the evaluation must consider
possible phase discrepancies. This is done with the aid of an AND-function for all three
phases in each apparatus for both open and close indications. Phase discrepancies will
result in an unknown double indication state.

Configuration guidelines

The following sections describe how the interlocking for a certain switchgear
configuration can be realized in the IED by using standard interlocking modules and
their interconnections. They also describe the configuration settings. The inputs for
delivery specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, except
in the following cases:
989_EX2 and 989_EX4 in modules BH_LINE_A and BH_LINE_B
152_EX3 in module AB_TRAFO
when they are set to 0=FALSE.
Interlocking for line bay ABC_LINE (3)
Application
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 238. The
function can also be used for a double busbar arrangement without transfer busbar or a
single busbar arrangement with/without transfer busbar.
289
189
189G
152
289G
989
ANSI04000478 V1 EN
Figure 238:
Switchyard layout ABC_LINE (3)
WA1 (A)
WA2 (B)
WA7 (C)
789
989G
en04000478_ansi.vsd