ABB RET670 Applications Manual page 594

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
588
Single circuit breaker with double busbar, internal voltage selection
Bus 1
Fuse
bus1 Voltage
VT
V REF 1
Fuse
bus2 Voltage
VT
V REF 2
lineVoltage /1/2/3
VA/VB/VC
ANSI10000095 V1 EN
Figure 228:
Connection of the SESRSYN function block in a single breaker, double
busbar arrangement with internal voltage selection
When internal voltage selection is needed, the voltage transformer circuit connections
are made according to figure 228. The voltage from the busbar 1 VT is connected to
U3PBB1 and the voltage from busbar 2 is connected to V3PBB2. The voltage from the
line VT is connected to V3PLN1. The positions of the disconnectors and VT fuses
shall be connected as shown in figure 228. The voltage selection parameter CBConfig
is set to Double bus.
Bus 2
189
289
152
Fuse
VT
Line
1MRK504116-UUS C
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI10000095-1-en.vsd
Application manual

Hide quick links:

Advertisement

Table of Contents
loading