insulated from the other by insulators because the can casing within each rack are at a
certain potential. Refer figure
Capacitor Unit
(Can)
IEC09000753 V1 EN
Figure 211:
Replacement of a faulty capacitor unit within SCB
There are four types of the capacitor unit fusing designs which are used for
construction of SCBs:
Externally
where an individual fuse, externally mounted, protects each capacitor unit.
fused
Internally fused
where each capacitor element is fused inside the capacitor unit
Fuseless
where SCB is built from series connections of the individual capacitor units (that is,
strings) and without any fuses
Unfused
where, in contrary to the fuseless configuration, a series or parallel connection of the
capacitor units is used to form SCB, still without any fuses
211
for an example:
Section 3
IED application
Rack
IEC09000753_1_en.vsd
495