Section 3
IED application
3.7.5.3
Table 98:
NS4PTOC (46I2) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
Table continues on next page
446
Reverse
Area
ANSI10000031 V1 EN
Figure 198:
Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
VPolMin: Minimum polarization (reference) voltage % of VBase.
I>Dir: Operate residual current level for directional comparison scheme. The setting is
given in % of IBase. The pickup forward or pickup reverse signals can be used in a
communication scheme. The appropriate signal must be configured to the
communication scheme block.

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
AngleRCA
Forward
Area
Iop = I2
Default
Description
Disabled
Disable/Enable Operation
3000
Base value for current settings
400
Base value for voltage settings
1MRK504116-UUS C
Vpol=-V2
ANSI10000031-1-en.vsd
Application manual