Table 81:
PSPPPAM (78) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationZ1
Disabled
Enabled
OperationZ2
Disabled
Enabled
ImpedanceZA
0.00 - 1000.00
ImpedanceZB
0.00 - 1000.00
ImpedanceZC
0.00 - 1000.00
AnglePhi
72.00 - 90.00
StartAngle
0.0 - 180.0
TripAngle
0.0 - 180.0
N1Limit
1 - 20
N2Limit
1 - 20
Table 82:
PSPPPAM (78) Group settings (advanced)
Name
Values (Range)
ResetTime
0.000 - 60.000
Table 83:
PSPPPAM (78) Non group settings (basic)
Name
Values (Range)
IBase
0.1 - 99999.9
Vbase
0.1 - 9999.9
MeasureMode
PosSeq
AB
BC
CA
InvertCTcurr
No
Yes
3.6.14
Application manual

Setting parameters

Unit
Step
-
-
-
-
-
-
%
0.01
%
0.01
%
0.01
Deg
0.01
Deg
0.1
Deg
0.1
-
1
-
1
Unit
Step
s
0.001
Unit
Step
A
0.1
kV
0.1
-
-
-
-

Phase preference logic PPLPHIZ

Function description
Phase preference logic
Default
Description
Disabled
Operation Enable / Disable
Enabled
Operation Enable/Disable zone Z1
Enabled
Operation Enable/Disable zone Z2
10.00
Forward impedance in % of Zbase
10.00
Reverse impedance in % of Zbase
10.00
Impedance of zone1 limit in % of Zbase
85.00
Angle of the slip impedance line
110.0
Rotor angle for the pickup signal
90.0
Rotor angle for the trip1 and trip2 signals
1
Count limit for the trip1 signal
3
Count limit for the trip2 signal
Default
Description
5.000
Time without slip to reset all signals
Default
Description
3000.0
Base Current (primary phase current in
Amperes)
20.0
Base Voltage (primary phase-to-phase
voltage in kV)
PosSeq
Measuring mode (PosSeq, AB, BC, CA)
No
Invert current direction
IEC 61850
IEC 60617
identification
identification
PPLPHIZ
Section 3
IED application
ANSI/IEEE C37.2
device number
-
-
389