Current Transformer Requirements For Cts According To Other Standards; Current Transformers According To Iec 60044-1, Class P, Pr - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
2.1.7
2.1.7.1
Application manual
connection) for example, in substations with breaker-and-a-half or double-busbar double-
breaker arrangement or if the transformer has a T-connection to different busbars, there
is a risk that the CTs can be exposed for higher fault currents than the considered phase-
to-ground fault currents above. Examples of such cases can be cross-country faults or
phase-to-phase faults with high fault currents and unsymmetrical distribution of the
phase currents between the CTs. The zero sequence fault current level can differ much
and is often difficult to calculate or estimate for different cases. To cover these cases,
with summation of zero sequence currents from more than one CT, the phase side CTs
must fulfill the Requirement (17) below:
æ
I
³
=
×
×
E
E
I
sn
ç
al
alreq
f
è
I
pn
EQUATION2242 V1 EN
Where:
I
Maximum primary fundamental frequency three-phase fault current that passes the
f
CTs (A)
R
The resistance of the secondary wire and additional load (Ω). The loop resistance
L
containing the phase and neutral wires shall be used.
Current transformer requirements for CTs according to other
standards
All kinds of conventional magnetic core CTs are possible to use with the IEDs if they
fulfill the requirements corresponding to the above specified expressed as the rated
equivalent secondary e.m.f. E
standards and available data for relaying applications it is possible to approximately
calculate a secondary e.m.f. of the CT comparable with E
required secondary e.m.f. E
requirements. The requirements according to some other standards are specified below.

Current transformers according to IEC 60044-1, class P, PR

A CT according to IEC 60044-1 is specified by the secondary limiting e.m.f. E
The value of the E
is approximately equal to the corresponding E
2max
IEC 60044-6. Therefore, the CTs according to class P and PR must have a secondary
limiting e.m.f. E
that fulfills the following:
2max
ö
S
+
+
R
R
R
÷
CT
L
2
ø
I
r
according to the IEC 60044-6 standard. From different
al
it is possible to judge if the CT fulfills the
alreq
Section 2
Requirements
(Equation 10)
. By comparing this with the
al
2max
according to
al
.
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents