Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
3.9.1.3
Table 139:
SAPTUF (81) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Vbase
0.05 - 2000.00
PUFrequency
35.00 - 75.00
IntBlockLevel
0 - 100
TimeDlyOperate
0.000 - 60.000
TimeDlyReset
0.000 - 60.000
TimeDlyRestore
0.000 - 60.000
RestoreFreq
45.00 - 65.00
TimerOperation
Definite timer
Volt based timer
VNom
50 - 150
VMin
50 - 150
Exponent
0.0 - 5.0
t_MaxTripDelay
0.010 - 60.000
t_MinTripDelay
0.010 - 60.000
544
Power system protection, by load shedding
The setting has to be well below the lowest occurring "normal" frequency and well
above the lowest acceptable frequency for power stations, or sensitive loads. The
setting level, the number of levels and the distance between two levels (in time and/or
in frequency) depends very much on the characteristics of the power system under
consideration. The size of the "largest loss of production" compared to "the size of the
power system" is a critical parameter. In large systems, the load shedding can be set at
a fairly high frequency level, and the time delay is normally not critical. In smaller
systems the frequency pickup level has to be set at a lower value, and the time delay
must be rather short.
The voltage related time delay is used for load shedding. The settings of the
underfrequency function could be the same all over the power system. The load
shedding is then performed firstly in areas with low voltage magnitude, which
normally are the most problematic areas, where the load shedding also is most efficient.

Setting parameters

Unit
Step
-
-
kV
0.05
Hz
0.01
%VB
1
s
0.001
s
0.001
s
0.001
Hz
0.01
-
-
%VB
1
%VB
1
-
0.1
s
0.001
s
0.001
Default
Description
Disabled
Disable/Enable Operation
400.00
Base voltage
48.80
Frequency setting pickup value.
50
Internal blocking level in % of VBase.
0.200
Operate time delay in over/under-frequency
mode.
0.000
Time delay for reset.
0.000
Restore time delay.
50.10
Restore frequency if frequency is above
frequency value.
Definite timer
Setting for choosing timer mode.
100
Nominal voltage in % of VBase for voltage
based timer.
90
Lower operation limit in % of VBase for
voltage based timer.
1.0
For calculation of the curve form for voltage
based timer.
1.000
Maximum time operation limit for voltage
based timer.
1.000
Minimum time operation limit for voltage
based timer.
1MRK504116-UUS C