Section 3
IED application
Name
Values (Range)
Angle2
-180.0 - 180.0
TripDelay2
0.010 - 6000.000
DropDelay2
0.010 - 6000.000
Table 115:
GOPPDOP (32) Group settings (advanced)
Name
Values (Range)
k
0.000 - 0.999
Hysteresis1
0.2 - 5.0
Hysteresis2
0.2 - 5.0
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
IMagComp100
-10.000 - 10.000
VMagComp5
-10.000 - 10.000
VMagComp30
-10.000 - 10.000
VMagComp100
-10.000 - 10.000
IAngComp5
-10.000 - 10.000
IAngComp30
-10.000 - 10.000
IAngComp100
-10.000 - 10.000
Table 116:
GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
IBase
1 - 99999
VBase
0.05 - 2000.00
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
492
Unit
Step
Default
Deg
0.1
0.0
s
0.001
1.000
s
0.001
0.060
Unit
Step
Default
-
0.001
0.000
pu
0.1
0.5
pu
0.1
0.5
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
Deg
0.001
0.000
Deg
0.001
0.000
Deg
0.001
0.000
Unit
Step
Default
A
1
3000
kV
0.05
400.00
-
-
Pos Seq
1MRK504116-UUS C
Description
Angle for stage 2
Trip delay for stage 2
Drop delay for stage 2
Description
Low pass filter coefficient for power
measurement, P and Q
Absolute hysteresis of stage 1 in % of Sbase
Absolute hysteresis of stage 2 in % of Sbase
Magnitude factor to calibrate current at 5% of
In
Magnitude factor to calibrate current at 30%
of In
Magnitude factor to calibrate current at 100%
of In
Magnitude factor to calibrate voltage at 5% of
Vn
Magnitude factor to calibrate voltage at 30%
of Vn
Magnitude factor to calibrate voltage at 100%
of Vn
Angle calibration for current at 5% of In
Angle calibration for current at 30% of In
Angle calibration for current at 100% of In
Description
Base setting for current level
Base setting for voltage level
Selection of measured current and voltage