ABB RET670 Applications Manual page 129

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
Table 39:
T3WPDIF (87T) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SOTFMode
Disabled
Enabled
tAlarmDelay
0.000 - 60.000
IDiffAlarm
0.05 - 1.00
IdMin
0.05 - 0.60
IdUnre
1.00 - 50.00
CrossBlockEn
Disabled
Enabled
NegSeqDiffEn
Disabled
Enabled
IMinNegSeq
0.02 - 0.20
NegSeqROA
30.0 - 120.0
Table 40:
T3WPDIF (87T) Group settings (advanced)
Name
Values (Range)
EndSection1
0.20 - 1.50
EndSection2
1.00 - 10.00
SlopeSection2
10.0 - 50.0
SlopeSection3
30.0 - 100.0
I2/I1Ratio
5.0 - 100.0
I5/I1Ratio
5.0 - 100.0
OpenCTEnable
Disabled
Enabled
tOCTAlarmDelay
0.100 - 10.000
tOCTResetDelay
0.100 - 10.000
tOCTUnrstDelay
0.10 - 6000.00
Application manual
Unit
Step
Default
-
-
Disabled
-
-
Enabled
s
0.001
10.000
IB
0.01
0.20
IB
0.01
0.30
IB
0.01
10.00
-
-
Enabled
-
-
Enabled
IB
0.01
0.04
Deg
0.1
60.0
Unit
Step
Default
IB
0.01
1.25
IB
0.01
3.00
%
0.1
40.0
%
0.1
80.0
%
0.1
15.0
%
0.1
25.0
-
-
Disabled
s
0.001
3.000
s
0.001
0.250
s
0.01
10.00
IED application
Description
Operation Disable / Enable
Operation mode for switch onto fault feature
Time delay for diff currents alarm level
Dif. cur. alarm, multiple of base curr, usually
W1 curr.
Section1 sensitivity, multi. of base curr,
usually W1 curr.
Unrestr. prot. limit, multi. of base curr. usually
W1 curr.
Operation Off/On for cross-block logic
between phases
Operation Off/On for neg. seq. differential
protections
Neg. seq. curr. limit, mult. of base curr,
usually W1 curr.
Operate Angle for internal / external negative
sequence fault discriminator
Description
End of section 1, multi. of base current,
usually W1 curr.
End of section 2, multi. of base current,
usually W1 curr.
Slope in section 2 of operate-restrain
characteristic, in %
Slope in section 3 of operate-restrain
characteristic, in %
Max. ratio of second harmonic to fundamental
harm dif. curr. in %
Max. ratio of fifth harmonic to fundamental
harm dif. curr. in %
Open CT detection feature. Open CTEnable
Off/On
Open CT: time in s to alarm after an open CT
is detected
Reset delay in s. After delay, diff. function is
activated
Unrestrained diff. protection blocked after this
delay, in s
Section 3