Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
3.12.1.4
Table 149:
SESRSYN (25) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CBConfig
No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
VBaseBus
0.001 - 9999.999
VBaseLine
0.001 - 9999.999
Table continues on next page
Application manual
VDeadBusEnerg and VDeadLineEnerg
The threshold voltages VDeadBusEnerg and VDeadLineEnerg, have to be set to a
value greater than the value where the network is considered not to be energized. A
typical value can be 40% of the base voltages.
A disconnected line can have a considerable potential due to, for
instance, induction from a line running in parallel, or by being fed via
the extinguishing capacitors in the circuit breakers. This voltage can be
as high as 30% or more of the base line voltage.
Because the setting ranges of the threshold voltages VLiveBusEnerg/VLiveLineEnerg
and VDeadBusEnerg/VDeadLineEnerg partly overlap each other, the setting conditions
may be such that the setting of the non-energized threshold value is higher than that of
the energized threshold value. The parameters must therefore be set carefully to avoid
the setting conditions mentioned above.
VMaxEnerg
This setting is used to block the closing when the voltage on the live side is above the
set value of VMaxEnerg.
tAutoEnerg and tManEnerg
The purpose of the timer delay settings, tAutoEnerg and tManEnerg, is to ensure that
the dead side remains de-energized and that the condition is not due to a temporary
interference. If the conditions do not persist for the specified time, the delay timer is
reset and the procedure is restarted when the conditions are fulfilled again. Circuit
breaker closing is thus not permitted until the energizing condition has remained
constant throughout the set delay setting time.

Setting parameters

Unit
Step
-
-
-
-
kV
0.001
kV
0.001
Default
Description
Disabled
Disable/Enable Operation
No voltage sel.
Select CB configuration
400.000
Base value for busbar voltage settings
400.000
Base value for line voltage settings
Section 3
IED application
599