ABB RET670 Applications Manual page 765

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
Application manual
Table 213:
General settings parameters for the Measurement function
Setting
Short description
Operation
Operation
PowAmpFact
Magnitude factor to scale power
calculations
PowAngComp
Angle compensation for phase
shift between measured I & V
Mode
Selection of measured current
and voltage
k
Low pass filter coefficient for
power measurement, V and I
VGenZeroDb
Zero point clamping in % of
Vbase
IGenZeroDb
Zero point clamping in % of Ibase
VBase
Base setting for voltage level in
kV
IBase
Base setting for current level in A
Measurement function application for a generator
Single line diagram for this application is given in figure 308.
Selected
value
Disabled / Enabled
Enabled
1.000
180.0
L1L2
0.00
25
3
35.00
495
Section 3
IED application
Comment
Enabled
Function must be
Typically no scaling is required
Typically no angle compensation is
required. However here the required
direction of P & Q measurement is
towards busbar (Not per IED internal
default direction). Therefore angle
compensation have to be used in
order to get measurements in aliment
with the required direction.
Only UL1L2 phase-to-phase voltage
is available
Typically no additional filtering is
required
Set minimum voltage level to 25%
Set minimum current level to 3%
Set LV side rated phase-to-phase
voltage
Set transformer LV winding rated
current
759

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents