Section 3
IED application
634
Application
The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one
bus-section disconnector between section 1 and 2 according to figure 253. A1A2_DC (3)
function can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1)
189G
ANSI04000492 V1 EN
Figure 253:
Switchyard layout A1A2_DC (3)
The signals from other bays connected to the module A1A2_DC are described below.
Signals in single breaker arrangement
If the busbar is divided by bus-section disconnectors, the condition no other
disconnector connected to the bus-section must be made by a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-
section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding
signals from busbar B are used.
Section 1
(WA1)A1
(WA2)B1
(WA7)C
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO
ABC_LINE
ANSI04000493 V1 EN
Figure 254:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from any bay that contains the above information.
WA2 (A2)
52
A1A2_DC
en04000492_ansi.vsd
Section 2
A2
B2
ABC_BC
ABC_LINE
1MRK504116-UUS C
289G
A3
B3
C
AB_TRAFO
en04000493_ansi.vsd
Application manual