Figure 108:
Measured impedance at voltage inversion
Forward direction:
Where
X
LLoc
X1
p
1,2
Compensated line with the series
capacitor not into the reach of zone 1.
The setting is thus:
X1
X
12
X
11
R
FW
X
C
equals line reactance up to the series capacitor(in the picture
approximate 33% of XLine)
is set to (XLindex-XC) · p/100.
is defined according to figure
is safety factor for fast operation of Zone 1
is set to (XLine-XC) · p/100.
Section 3
IED application
R
en06000584.vsd
106
241