Section 3
IED application
336
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
2
æ
X
m0
×
R
R
ç
1
------------------------- -
=
+
0E
0
2
è
R
X
+
0
0
EQUATION561 V1 EN
2
æ
X
m0
×
------------------------- -
X
=
X
ç
1
0E
0
2
2
è
R
+
X
0
0
EQUATION562 V1 EN
Setting of reach in resistive direction
Set the resistive independently for each zone.
Set separately the expected fault resistance for phase-to-phase faults RFPP and for the
phase-to-ground faults RFPG for each zone. For each distance zone, set all remaining
reach setting parameters independently of each other.
The final reach in resistive direction for phase-to-ground fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance, and
at the end of the protected zone is equal to equation 86.
1
(
)
=
×
+
+
R
2 R1 R0
RFPG
3
ANSIEQUATION2303 V1 EN
é
×
+
2 X1 X0
j
=
loop
arctan
ê
ë
×
+
2 R1 R0
EQUATION2304 V1 EN
Setting of the resistive reach for the underreaching zone 1 should follow the condition
to minimize the risk for overreaching:
£
×
RFPG
4.5 X1
ANSIEQUATION2305 V1 EN
The fault resistance for phase-to-phase faults is normally quite low, compared to the
fault resistance for phase-to-ground faults. To minimize the risk for overreaching, limit
the setting of the zone1 reach in resistive direction for phase-to-phase loop
measurement to:
ö
÷
2
ø
ö
÷
ø
ù
ú
û
1MRK504116-UUS C
(Equation 270)
(Equation 271)
(Equation 272)
(Equation 273)
(Equation 274)
Application manual