Setting parameters

The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
Boolean 16 to Integer conversion B16I
Function description
Boolean 16 to integer conversion
Application
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary
(logical) signals into an integer. It can be used – for example, to connect logical output
signals from a function (like distance protection) to integer inputs from another
function (like line differential protection). B16I does not have a logical node mapping.
Setting guidelines
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
Boolean 16 to Integer conversion with logic node
representation B16IFCVI
Function description
Boolean 16 to integer conversion with
logic node representation
Application
Boolean 16 to integer conversion with logic node representation function B16IFCVI is
used to transform a set of 16 binary (logical) signals into an integer. B16IFCVI can
receive an integer from a station computer – for example, over IEC 61850–8–1. These
functions are very useful when you want to generate logical commands (for selector
switches or voltage controllers) by inputting an integer number. B16IFCVI has a
logical node mapping in IEC 61850.
IEC 61850
IEC 60617
identification
identification
B16I
-
IEC 61850
IEC 60617
identification
identification
B16IFCVI
-
1MRK504116-UUS C
ANSI/IEEE C37.2
device number
-
ANSI/IEEE C37.2
device number
-
Application manual