Section 3
IED application
266
LdAngle
LdAngle
RLd
ANSI06000404 V1 EN
Figure 116:
Load encroachment of Faulty phase identification with load
encroachment for mho function FMPSPDIS (21) characteristic
The use of the load encroachment feature is essential for long heavy loaded lines,
where there might be a conflict between the necessary emergency load transfer and
necessary sensitivity of the distance protection. The function can also preferably be
used on heavy loaded medium long lines. For short lines the major concern is to get
sufficient fault resistance coverage and load encroachment is not a major problem. So,
for short lines, the load encroachment function could preferably be switched off.
The main settings of the parameters for load encroachment are done in Faulty phase
identification with load encroachment for mho function FMPSPDIS (21). The
operation of load encroachment function is always activated. To deactivate the
function, setting LoadEnchMode should be set off or the setting of RLdFw and RLdRv
must be set to a value much higher than the maximal load impedance.
Short line application
The definition of short, medium and long lines is found in IEEE Std C37.113-1999.
The length classification is defined by the ratio of the source impedance at the
protected line's terminal to the protected line's impedance (SIR). SIR's of about 4 or
greater generally define a short line. Medium lines are those with SIR's greater than
0.5 and less than 4.
X
RLd
LdAngle
R
LdAngle
en06000404_ansi.vsd
1MRK504116-UUS C
Application manual