Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
3.13.1.3
Table 198:
ECPSCH (85) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SchemeType
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord
0.000 - 60.000
tSendMin
0.000 - 60.000
Table 199:
ECPSCH (85) Group settings (advanced)
Name
Values (Range)
Unblock
Disabled
NoRestart
Restart
tSecurity
0.000 - 60.000
3.13.2
Application manual
tCoord: Delay time for trip from ECPSCH (85) function. For Permissive under/
overreaching schemes, this timer shall be set to at least 20 ms plus maximum reset time
of the communication channel as a security margin. For Blocking scheme, the setting
should be > maximum signal transmission time +10 ms.
Unblock: Select Off if unblocking scheme with no alarm for loss of guard is used. Set
to Restart if unblocking scheme with alarm for loss of guard is used.

Setting parameters

Unit
Step
-
-
-
-
s
0.001
s
0.001
Unit
Step
-
-
s
0.001
Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH (85)
Function description
Current reversal and weak-end infeed
logic for residual overcurrent protection
Default
Description
Disabled
Disable/Enable Operation
Permissive UR
Scheme type, Mode of Operation
0.035
Communication scheme channel coordination
time
0.100
Minimum duration of a carrier send signal
(carrier continuation)
Default
Description
Disabled
Operation mode of unblocking logic
0.035
Security timer for loss of carrier guard detection
IEC 61850
IEC 60617
identification
identification
ECRWPSCH
Section 3
IED application
ANSI/IEEE C37.2
device number
-
85
731

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents