ABB RET670 Applications Manual page 766

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
760
230kV Busbar
300/5
100 MVA
15/0.12kV
P
Q
100 MVA
G
15.65kV
4000/5
ANSI09000041 V1 EN
Figure 308:
Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 308, it is
necessary to do the following:
1.
Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef(see section
channels
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the
following table:
IED
V
V
,
AB ,
BC
ANSI09000041-1-en.vsd
"Analog
inputs") using PCM600 for analog input
1MRK504116-UUS C
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents