Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
3.11.2.3
Table 148:
SDDRFUF Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
3V0PU
1 - 100
Table continues on next page
578
VSetprim
=
×
DVPU
100
VBase
EQUATION1765-ANSI V1 EN
ISetprim
DIPU
100
=
×
IBase
ANSIEQUATION2385 V1 EN
The voltage thresholds VPPU is used to identify low voltage condition in the system.
Set VPPU below the minimum operating voltage that might occur during emergency
conditions. A setting of approximately 70% of VBase is recommended.
The current threshold 50P shall be set lower than the IMinOp for the distance
protection function. A 5...10% lower value is recommended.
Dead line detection
The condition for operation of the dead line detection is set by the parameters IDLDPU
for the current threshold and VDLDPU for the voltage threshold.
Set the IDLDPU with a sufficient margin below the minimum expected load current. A
safety margin of at least 15-20% is recommended. The operate value must however
exceed the maximum charging current of an overhead line, when only one phase is
disconnected (mutual coupling to the other phases).
Set the VDLDPU with a sufficient margin below the minimum expected operating
voltage. A safety margin of at least 15% is recommended.

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
-
-
%VB
1
Default
Description
Enabled
Disable/Enable Operation
3000
Base current
400.00
Base voltage
V0I0
Operating mode selection
30
Pickup of residual overvoltage element in %
of VBase
1MRK504116-UUS C
(Equation 418)
(Equation 419)
Application manual