Section 3
IED application
618
The signals from other bays connected to the module ABC_LINE (3) are described below.
Signals from bypass busbar
To derive the signals:
Signal
BB7_D_OP
All line disconnectors on bypass WA7 except in the own bay are open.
VP_BB7_D
The switch status of disconnectors on bypass busbar WA7 are valid.
EXDU_BPB
No transmission error from any bay containing disconnectors on bypass busbar WA7
These signals from each line bay (ABC_LINE, 3) except that of the own bay are needed:
Signal
789OPTR
789 is open
VP789TR
The switch status for 789 is valid.
EXDU_BPB
No transmission error from the bay that contains the above information.
For bay n, these conditions are valid:
789OPTR (bay 1)
789OPTR (bay 2)
. . .
. . .
789OPTR (bay n-1)
VP789TR (bay 1)
VP789TR (bay 2)
. . .
. . .
VP789TR (bay n-1)
EXDU_BPB (bay 1)
EXDU_BPB (bay 2)
. . .
. . .
EXDU_BPB (bay n-1)
ANSI04000477 V1 EN
Figure 239:
Signals from bypass busbar in line bay n
BB7_D_OP
AND
VP_BB7_D
AND
EXDU_BPB
AND
en04000477_ansi.vsd
1MRK504116-UUS C
Application manual