ABB RET670 Applications Manual page 267

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
Application manual
System grounding
The type of system grounding plays an important role when designing the protection
system. In the following some hints with respect to distance protection are highlighted.
Solid grounded networks
In solid grounded systems the transformer neutrals are connected solidly to ground
without any impedance between the transformer neutral and ground.
ANSI05000215 V1 EN
Figure 112:
Solidly grounded network
The ground-fault current is as high as or even higher than the short-circuit current. The
series impedances determine the magnitude of the ground-fault current. The shunt
admittance has very limited influence on the ground-fault current. The shunt
admittance may, however, have some marginal influence on the ground-fault current in
networks with long transmission lines.
The ground-fault current at single phase-to-ground in phase A can be calculated as
equation 177:
× V
3
=
A
3I
0
Z
+Z
+Z
+3Z
1
2
0
EQUATION1748-ANSI V2 EN
Where:
V
is the phase to ground voltage (kV) in the faulty phase before fault
A
Z
is the positive sequence impedance (Ω/phase)
1
Z
is the negative sequence impedance (Ω/phase)
2
Z
is the zero sequence impedance (Ω/phase)
0
Z
is the fault impedance (Ω), often resistive
f
Z
is the ground return impedance defined as (Z
N
The voltage on the healthy phases is generally lower than 140% of the nominal phase-to-
ground voltage. This corresponds to about 80% of the nominal phase-to-phase voltage.
V
=
A
Z
+Z
+Z
f
f
N
1
-Z
)/3
0
1
Section 3
IED application
xx05000215_ansi.vsd
(Equation 177)
261

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents