ABB RET670 Applications Manual page 238

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
232
ordinary fault. However, a good protection system should be able to operate correctly
before and after gap flashing occurs.
jX
X
12
X
11
Z
S
X
C
en06000625.vsd
IEC06000625 V1 EN
Figure 100:
Cross-polarized
quadrilateral
characteristic
If the distance protection is equipped with a ground-fault measuring unit, the negative
impedance occurs when
×
>
×
+
3
X
2
X
X
C
1 _ 11
0 _ 11
EQUATION1919 V1 EN
Cross-polarized distance protection (either with mho or quadrilateral characteristic)
will normally handle ground-faults satisfactory if the negative impedance occurs inside
the characteristic. The operating area for negative impedance depends upon the
magnitude of the source impedance and calculations must be made on a case by case
basis, as shown in figure 100. Distance IEDs with separate impedance and directional
measurement offer additional setting and operational flexibility when it comes to
measurement of negative apparent impedance (as shown in figure 101).
Negative IED impedance, negative fault current (current inversion)
If equation
148
>
+
XC
X
X
S
l1
EQUATION2036 V1 EN
jX
R
RV
R
Z
S
IEC06000584-SMALL V1 EN
Figure 101:
1MRK504116-UUS C
X
12
X
11
R
R
FW
X
C
en06000584_small.vsd
Quadrilateral
characteristic with
separate impedance
and directional
measurement
(Equation 147)
(Equation 148)
Application manual