ABB RET670 Applications Manual page 606

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
Name
Values (Range)
PhaseShift
-180 - 180
VRatio
0.040 - 25.000
OperationSynch
Disabled
Enabled
VHighBusSynch
50.0 - 120.0
VHighLineSynch
50.0 - 120.0
VDiffSynch
0.02 - 0.50
FreqDiffMin
0.003 - 0.250
FreqDiffMax
0.050 - 0.250
FreqRateChange
0.000 - 0.500
tBreaker
0.000 - 60.000
tClosePulse
0.050 - 60.000
tMaxSynch
0.00 - 6000.00
tMinSynch
0.000 - 60.000
OperationSC
Disabled
Enabled
VHighBusSC
50.0 - 120.0
VHighLineSC
50.0 - 120.0
VDiffSC
0.02 - 0.50
FreqDiffA
0.003 - 1.000
FreqDiffM
0.003 - 1.000
PhaseDiffA
5.0 - 90.0
PhaseDiffM
5.0 - 90.0
tSCA
0.000 - 60.000
tSCM
0.000 - 60.000
AutoEnerg
Disabled
DLLB
DBLL
Both
Table continues on next page
600
Unit
Step
Default
Deg
5
0
-
0.001
1.000
-
-
Disabled
%VBB
1.0
80.0
%VBL
1.0
80.0
pu
0.01
0.10
Hz
0.001
0.010
Hz
0.001
0.200
Hz/s
0.001
0.300
s
0.001
0.080
s
0.001
0.200
s
0.01
600.00
s
0.001
2.000
-
-
Enabled
%VBB
1.0
80.0
%VBL
1.0
80.0
pu
0.01
0.15
Hz
0.001
0.010
Hz
0.001
0.010
Deg
1.0
25.0
Deg
1.0
25.0
s
0.001
0.100
s
0.001
0.100
-
-
DBLL
1MRK504116-UUS C
Description
Phase shift
Voltage ratio
Operation for synchronizing function Off/On
Voltage high limit bus for synchronizing in %
of UBaseBus
Voltage high limit line for synchrocheck in %
of VBaseLine
Voltage difference limit for synchronizing in p.u
Minimum frequency difference limit for
synchronizing
Maximum frequency difference limit for
synchronizing
Maximum allowed frequency rate of change
Closing time of the breaker
Breaker closing pulse duration
Resets synch if no close has been made
before set time
Minimum time to accept synchronizing
conditions
Operation for synchronism-check function Off/
On
Voltage high limit bus for synchrocheck in %
of VBaseBus
Voltage high limit line for synchrocheck in %
of UBaseLine
Voltage difference limit in p.u
Frequency difference limit between bus and
line Auto
Frequency difference limit between bus and
line Manual
Phase angle difference limit between bus and
line Auto
Phase angle difference limit between bus and
line Manual
Time delay output for synchrocheck Auto
Time delay output for synchrocheck Manual
Automatic energizing check mode
Application manual