Application manual
outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used. Together with
the configuration logic circuits, the user can govern pulses or steady output signals for
control purposes within the IED or via binary outputs.
Figure
293
shows an application example of how the user can connect SINGLECMD
via configuration logic circuit to control a high-voltage apparatus. This type of
command control is normally carried out by sending a pulse to the binary outputs of
the IED. Figure
293
shows a close operation. An open breaker operation is performed
in a similar way but without the synchro-check condition.
Single
command
function
SINGLECMD
Close CB1
CMDOUTy
OUTy
ANSI04000206 V2 EN
Figure 293:
Application example showing a logic diagram for control of a circuit
breaker via configuration logic circuits
Figure
294
and figure
295
Enabled/Disabled signals. Here, the output is used to control built-in functions or
external devices.
Configuration logic circuits
User-
AND
defined
conditions
Synchro-
check
show other ways to control functions, which require steady
Section 3
IED application
en04000206_ansi.vsd
727