ABB RET670 Product Manual
ABB RET670 Product Manual

ABB RET670 Product Manual

Relion 670 series transformer protection 9-2 le customized
Hide thumbs Also See for RET670:

Advertisement

®
Relion
670 series
Transformer protection RET670 9-2 LE
Customized
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RET670

  • Page 1 ® Relion 670 series Transformer protection RET670 9-2 LE Customized Product Guide...
  • Page 2: Table Of Contents

    18. Ordering..............59 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.
  • Page 3: Application

    IED the ideal solution even for the most demanding system. applications. Since RET670 has very low requirements on the main CTs, no interposing CTs are required.It is suitable for Versatile phase, earth, positive and zero sequence...
  • Page 4 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 TRIP BUSBAR 50BF 3I> 1-ph 1-ph 51/67 3I> 94/86 TRIP CB1 Merging I->O unit 51N/67N IN> IdN/I> 3Id/I> IdN/I> 51N/67N IN> 51/67 3I> 94/86 50BF TRIP CB2 I->O 3I>...
  • Page 5 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Merging Merging unit 51/67 unit 3I> 94/86 TRIP CB1 I->O 51N/67N 94/86 IN> TRIP CB2 I->O IdN/I> 3Id/I> IdN/I> 51N/67N IN> 51/67 3I> 94/86 TRIP CB3 50BF I->O 3I>...
  • Page 6 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 51/67 Merging 3I> 94/86 unit TRIP CB1 I->O 51N/67N IN> IdN/I> 3Id/I> 50BF IdN/I> TRIP BUSBAR 3I> &CB1/2 51N/67N IN> 3I> 51/67 3I> 94/86 TRIP 94/86 I->O TRIP CB2 50BF I->O...
  • Page 7 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Merging Merging unit 51/67 unit MU2 3I> 94/86 TRIP CB1 I->O 51N/67N 94/86 IN> TRIP CB2 I->O IdN/I> 3Id/I> 50BF IdN/I> TRIP BUSBAR 3I> &CB1/2/3 51N/67N IN> 3I> 51/67 3I>...
  • Page 8: Available Functions

    Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 2. Available functions Main protection functions = number of basic instances IEC 61850 ANSI Function description Transformer Differential protection T2WPDIF Transformer differential protection, two winding T3WPDIF Transformer differential protection, three winding...
  • Page 9: Secondary System Supervision

    Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Transformer Control SESRSYN Synchrocheck, energizing check and synchronizing QCBAY Apparatus control LOCREM Handling of LRswitch positions LOCREMCTR LHMI control of PSTO...
  • Page 10: Metering

    Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 IEC 61850 ANSI Function description Transformer BSStatReport Logical signal status report RANGE_XP Measured value expander block Metering PCGGIO Pulse-counter logic ETPMMTR Function for energy calculation and demand handling Designed to communicate...
  • Page 11: Basic Ied Functions

    Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup...
  • Page 12 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 high set unrestrained differential current protection element is included for a very high speed tripping at a high internal fault Two-winding applications currents. two-winding power transformer Included is an innovative sensitive differential protection xx08000153.vsd...
  • Page 13 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 5. Current protection Instantaneous phase overcurrent protection PHPIOC The instantaneous three phase overcurrent function has a low Forward transient overreach and short tripping time to allow use as a operation high set short-circuit protection function.
  • Page 14 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 prepare for system restoration at power outages or as long- Thermal overload protection, two time constant TRPTTR time delayed back-up to primary protection. If a power transformer or generator reaches very high temperatures the equipment might be damaged.
  • Page 15 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 7. Secondary system supervision For systems which are running asynchronous a synchronizing function is provided. The main purpose of the synchronizing Fuse failure supervision SDDRFUF function is to provide controlled closing of circuit breakers The aim of the fuse failure supervision function (SDDRFUF) is when two asynchronous systems are going to be connected.
  • Page 16 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 control high voltage apparatuses or for other user defined signals connected to the function block with a, maximum of functionality. 40 analog and 96 binary signals. The Disturbance report functionality is a common name for 9.
  • Page 17 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 term (for example corrective actions) and in the long term (for Analog and double indication values are also transferred example functional analysis). through EVENT function. The event recorder logs all selected binary input signals IEC61850 generic communication I/O functions MVGGIO connected to the Disturbance report function.
  • Page 18: Human Machine Interface

    ABB IED's and the new IED 670. SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation Monitoring Systems SMS.
  • Page 19 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Binary input module BIM module has two optical communication ports for plastic/ The binary input module has 16 optically isolated inputs and plastic, plastic/glass or glass/glass. One port is used for serial...
  • Page 20 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Dimensions xx05000059.vsd IEC05000059 V1 EN Figure 9. 1/1 x 19” case with rear cover Case size 6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3 (mm) Mounting alternatives See ordering for details about available mounting alternatives.
  • Page 21: Connection Diagrams

    Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 16. Connection diagrams Table 1. Designations for 1/1 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X161 IOM or MIM...
  • Page 22 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 1MRK002801-AC-10-670-1.2-PG V1 EN Figure 10. Transformer input module (TRM) ■ Indicates high polarity CT/VT-input designation according to figure AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11...
  • Page 23 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 1MRK002801-AC-15-670-1.2-PG V1 EN Figure 12. mA input module (MIM) 1MRK002801-AC-11-670-1.2-PG V1 EN Figure 11. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, and so on, and input contacts named XB to rear position X32, X42, and so on.
  • Page 24 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 1MRK002801-AC-7-670-1.2-PG V1 EN Figure 14. Power supply module (PSM) 1MRK002801-AC-12-670-1.2-PG V1 EN Figure 15. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output...
  • Page 25 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 1MRK002801-AC-13-670-1.2-PG V1 EN Figure 16. Static output module (SOM) 1MRK002801-AC-14-670-1.2-PG V1 EN Figure 17. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts...
  • Page 26: Technical Data

    Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 17. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the...
  • Page 27 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 3. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×...
  • Page 28 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Binary inputs and outputs Table 6. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ± 20% 110/125 V RL ±...
  • Page 29 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 8. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ± 20% 110/125 V RL ±...
  • Page 30 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 10. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
  • Page 31 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 12. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC Number of outputs...
  • Page 32 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 15. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% /%...
  • Page 33 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Type tests according to standards Table 17. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-22-1 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
  • Page 34 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 19. Environmental tests Test Type test value Reference standard Cold test Test Ad for 16 h at -25°C IEC 60068-2-1 Storage test Test Ad for 16 h at -40°C...
  • Page 35 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Differential protection Table 22. Transformer differential protection T2WPDIF, T3WPDIF Function Range or value Accuracy Operating characteristic Adaptable ± 1.0% of Ir for I < Ir ± 1.0% of I for I > Ir Reset ratio >95%...
  • Page 36 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Impedance protection Table 24. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones 4 with selectable direction Minimum operate residual...
  • Page 37 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Current protection Table 26. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 38 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 28. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 39 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 30. Thermal overload protection, two time constants TRPTTR Function Range or value Accuracy Base current 1 and 2 (30–250)% of IBase ± 1.0% of I Operate time: = load current before overload IEC 60255–8, ±5% + 200 ms...
  • Page 40 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Voltage protection Table 33. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1–100)% of ± 0.5% of U UBase Absolute hysteresis (0–100)% of...
  • Page 41 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 35. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 and step 2 (1-200)% of UBase ± 0.5% of U at U < U ±...
  • Page 42 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Secondary system supervision Table 38. Fuse failure supervision SDDRFUF Function Range or value Accuracy Operate voltage, zero sequence (1-100)% of UBase ± 1.0% of U Operate current, zero sequence (1–100)% of IBase...
  • Page 43 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Control Table 39. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, U 0.500 - 2.000 line...
  • Page 44 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Logic Table 40. Tripping logic SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms Timers (0.000-60.000) s ±...
  • Page 45 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Monitoring Table 42. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Voltage (0.1-1.5) ×U ± 0.5% of U at U£U ± 0.5% of U at U > U Connected current (0.2-4.0) ×...
  • Page 46 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 46. Current sequence component measurement CMSQI Function Range or value Accuracy Current positive sequence, I1 (0.1–4.0) × I ± 0.2% of I at I ≤ 0.5 × I Three phase settings ±...
  • Page 47 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 50. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
  • Page 48 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 54. Trip value recorder Function Value Buffer capacity Maximum number of analog inputs Maximum number of disturbance reports Table 55. Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs...
  • Page 49 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Metering Table 56. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 57. Energy metering ETPMMTR...
  • Page 50 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Station communication Table 58. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 608–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
  • Page 51 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 64. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fibre: type ST Plastic fibre: type HFBR snap-in Fibre, optical budget Glass fibre: 11 dB (3000ft/1000 m typically *)
  • Page 52 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Hardware Table 66. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 67. Water and dust protection level according to IEC 60529...
  • Page 53 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Basic IED functions Table 71. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 72. Time synchronization, time tagging...
  • Page 54 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Inverse characteristic Table 74. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷...
  • Page 55 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 75. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø...
  • Page 56 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 77. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö >...
  • Page 57 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 78. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö < - ç...
  • Page 58 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Table 79. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 5% +40 ms 0.01 æ ö...
  • Page 59: Ordering

    Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 18. Ordering Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections.
  • Page 60 ANSI 1/1 19" 1MRK 000 008-MC Analog system for RET670 V1 61850-9-2LE Note: Only one alternative must be ordered. The same type of connection terminals has to be ordered for both TRMs. Standard: Rule: One function within the alternative must be ordered...
  • Page 61 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Maximum quantity of I/O modules, with ring lug terminals, module limits see above Case sizes Maximum in case Possible locations for I/O modules with ringlugs 1/1 x 19”, one (1) TRM...
  • Page 62 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Binary input/output modules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 63 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 RL 24-30 VDC Qty: 1MRK 000 508-HA 10 11 12 13 RL 48-60 VDC Qty: 1MRK 000 508-EA 10 11 12 13 RL 110-125 VDC Qty: 1MRK 000 508-FA...
  • Page 64 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 65 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 Flush mounting kit for terminal Quantity: 1MRK 000 020-Y Flush mounting kit + IP54 sealing (factory mounted). Cannot be ordered separately thus must be Quantity: 1MRK 002 420-EA specified when ordering a terminal.
  • Page 66 Transformer protection RET670 9-2 LE 1MRK504119-BEN B Customized Product version: 1.2 User documentation Rule: Specify the number of printed manuals requested Operator’s manual Quantity: 1MRK 504 114-UEN ANSI Quantity: 1MRK 504 114-UUS Technical reference manual Quantity: 1MRK 504 113-UEN ANSI...
  • Page 67 670 series SPA and signal list 1MRK 500 092-WEN IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN Engineering manual 670 series 1MRK 511 240-UEN Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 69 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...