Section 3
IED application
666
The calculated mean busbar voltage V
value BusVolt under Main menu/Test/Function status/Control/
TransformerVoltageControl(ATCC,90)/TR8ATCC:x.
Measured current values for the individual transformers must be communicated
between the participating TR8ATCC (90) functions, in order to calculate the
circulating current.
The calculated circulating current I
service value ICIRCUL under Main menu/Test/Function status/Control/
TransformerVoltageControl(ATCC,90)/TR8ATCC:x.
When the circulating current is known, it is possible to calculate a no-load voltage for
each transformer in the parallel group. To do that the magnitude of the circulating
current in each bay, is first converted to a voltage deviation, V
=
×
×
C I
X
V
di
i
cc _ i
i
EQUATION1979-ANSI V1 EN
where X
is the short-circuit reactance for transformer i and C
i
named Comp which serves the purpose of alternatively increasing or decreasing the
impact of the circulating current in TR8ATCC control calculations. It should be noted
that V
will have positive values for transformers that produce circulating currents and
di
negative values for transformers that receive circulating currents.
Now the magnitude of the no-load voltage for each transformer can be approximated
with:
=
+
V
V
V
i
Bmean
di
EQUATION1980-ANSI V1 EN
This value for the no-load voltage is then simply put into the voltage control function
for single transformer. There it is treated as the measured busbar voltage, and further
control actions are taken as described previously in section
for a single
transformer". By doing this, the overall control strategy can be summarized
as follows.
For the transformer producing/receiving the circulating current, the calculated no-load
voltage will be greater/smaller than the measured voltage V
load voltage will then be compared with the set voltage VSet. A steady deviation which
is outside the outer deadband will result in VLOWER or VRAISE being initiated
alternatively. In this way the overall control action will always be correct since the
position of a tap changer is directly proportional to the transformer no-load voltage.
The sequence resets when V
is shown on the local HMI as a service
Bmean
for transformer "i" is shown on the HMI as a
cc_i
is inside the inner deadband at the same time as the
Bmean
1MRK504116-UUS C
, with equation 424:
di
(Equation 424)
, is a setting parameter
i
(Equation 425)
"Automatic voltage control
. The calculated no-
Bmean
Application manual