Table 224:
CMSQI Non group settings (advanced)
Name
Values (Range)
3I0ZeroDb
0 - 100000
3I0HiHiLim
0.000 -
10000000000.000
3I0HiLim
0.000 -
10000000000.000
3I0LowLim
0.000 -
10000000000.000
3I0LowLowLim
0.000 -
10000000000.000
3I0AngZeroDb
0 - 100000
I1ZeroDb
0 - 100000
I1HiHiLim
0.000 -
10000000000.000
I1HiLim
0.000 -
10000000000.000
I1LowLim
0.000 -
10000000000.000
I1LowLowLim
0.000 -
10000000000.000
I1LimHys
0.000 - 100.000
I1AngZeroDb
0 - 100000
I1AngMin
-180.000 - 180.000
I2ZeroDb
0 - 100000
I2HiHiLim
0.000 -
10000000000.000
I2HiLim
0.000 -
10000000000.000
I2LowLim
0.000 -
10000000000.000
I2LowLowLim
0.000 -
10000000000.000
I2AngZeroDb
0 - 100000
I2AngMax
-180.000 - 180.000
772
Unit
Step
Default
m%
1
0
A
0.001
900.000
A
0.001
800.000
A
0.001
0.000
A
0.001
0.000
m%
1
0
m%
1
0
A
0.001
900.000
A
0.001
800.000
A
0.001
0.000
A
0.001
0.000
%
0.001
5.000
m%
1
0
Deg
0.001
-180.000
m%
1
0
A
0.001
900.000
A
0.001
800.000
A
0.001
0.000
A
0.001
0.000
m%
1
0
Deg
0.001
180.000
1MRK504116-UUS C
Description
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Zero point clamping in 0.001% of range
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0.001% of range
Minimum value
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Zero point clamping in 0.001% of range
Maximum value