IEC 61850 generic communication I/O functions SPGGIO,
SP16GGIO
Application
IEC 61850–8–1 generic communication I/O functions (SPGGIO) function is used to
send one single logical output to other systems or equipment in the substation. It has
one visible input, that should be connected in ACT tool.
Setting guidelines
There are no settings available for the user for SPGGIO. However, PCM600 must be
used to get the signals sent by SPGGIO.
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
IEC 61850 generic communication I/O functions MVGGIO
Application
IEC61850 generic communication I/O functions (MVGGIO) function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
Setting guidelines
The settings available for IEC61850 generic communication I/O functions (MVGGIO)
function allows the user to choose a deadband and a zero deadband for the monitored
signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low
and low-low ranges of the measured value. The actual range of the measured value is
shown on the range output of MVGGIO function block. When a Measured value
expander block (RANGE_XP) is connected to the range output, the logical outputs of
the RANGE_XP are changed accordingly.
1MRK504116-UUS C
Application manual