ABB RET670 Applications Manual page 776

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
Name
Values (Range)
VMagComp100
-10.000 - 10.000
VAB_Min
0.000 -
10000000000.000
VAB_LimHys
0.000 - 100.000
VBC_ZeroDb
0 - 100000
VBC_HiHiLim
0.000 -
10000000000.000
VBC_HiLim
0.000 -
10000000000.000
VBC_LowLim
0.000 -
10000000000.000
VBC_LowLowLim
0.000 -
10000000000.000
VBC_Min
0.000 -
10000000000.000
VBC_LimHys
0.000 - 100.000
VCA_ZeroDb
0 - 100000
VCA_HiHiLim
0.000 -
10000000000.000
VCA_HiLim
0.000 -
10000000000.000
VCA_LowLim
0.000 -
10000000000.000
VCA_LowLowLim
0.000 -
10000000000.000
VCA_Min
0.000 -
10000000000.000
VCA_LimHys
0.000 - 100.000
Table 223:
CMSQI Non group settings (basic)
Name
Values (Range)
3I0DbRepInt
1 - 300
3I0Min
0.000 -
10000000000.000
3I0Max
0.000 -
10000000000.000
Table continues on next page
770
Unit
Step
Default
%
0.001
0.000
V
0.001
0.000
%
0.001
5.000
m%
1
0
V
0.001
450000.000
V
0.001
420000.000
V
0.001
380000.000
V
0.001
350000.000
V
0.001
0.000
%
0.001
5.000
m%
1
0
V
0.001
450000.000
V
0.001
420000.000
V
0.001
380000.000
V
0.001
350000.000
V
0.001
0.000
%
0.001
5.000
Unit
Step
Default
Type
1
10
A
0.001
0.000
A
0.001
1000.000
1MRK504116-UUS C
Description
Magnitude factor to calibrate voltage at 100%
of Vn
Minimum value
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Hysteresis value in % of range and is
common for all limits
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Minimum value
Maximum value
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents