Section 4 Analog Inputs; Introduction; Setting Guidelines; Setting Of The Phase Reference Channel - ABB RELION 670 SERIES REG670 Applications Manual

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

1MRK 502 071-UUS A
Section 4
4.1
4.2
4.2.1
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Analog inputs

Introduction

Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring, all
directional and differential functions, the directions of the input currents must be
defined in order to reflect the way the current transformers are installed/connected in
the field ( primary and secondary connections ). Measuring and protection algorithms
in the IED use primary system quantities. Setting values are in primary quantities as
well and it is important to set the data about the connected current and voltage
transformers properly.
An AISVBAS reference PhaseAngleRef can be defined to facilitate service values
reading. This analog channel's phase angle will always be fixed to zero degrees and
remaining analog channel's phase angle information will be shown in relation to this
analog input. During testing and commissioning of the IED, the reference channel can
be changed to facilitate testing and service values reading.
The availability of VT inputs depends on the ordered transformer input
module (TRM) type.

Setting guidelines

The available setting parameters related to analog inputs are depending
on the actual hardware (TRM) and the logic configuration made in
PCM600.

Setting of the phase reference channel

All phase angles are calculated in relation to a defined reference. An appropriate
analog input channel is selected and used as phase reference. The parameter
PhaseAngleRef defines the analog channel that is used as phase angle reference.
Section 4
Analog inputs
SEMOD55003-5 v11
SEMOD55068-1 v1
SEMOD130348-4 v4
SEMOD55055-5 v3
67

Advertisement

Table of Contents
loading

Table of Contents