Additional Distance Protection Directional Function For Earth Faults Zdardir; Application; Setting Guidelines - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
Name
Values (Range)
OperationDir
Disabled
Non-directional
Forward
Reverse
X1
0.50 - 3000.00
R1
0.10 - 1000.00
X0
0.50 - 9000.00
R0
0.50 - 3000.00
RFPG
1.00 - 9000.00
Timer tPG
Disabled
Enabled
tPG
0.000 - 60.000
IMinPUPG
10 - 30
3.6.6
3.6.6.1
3.6.6.2
306
Unit
Step
-
-
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/l
0.01
-
-
s
0.001
%IB
1
Additional distance protection directional function for earth
faults ZDARDIR
Function description
Additional distance protection
directional function for earth faults

Application

The phase-to-ground impedance elements can be optionally supervised by a phase
unselective directional function based on symmetrical components.

Setting guidelines

AngleRCA and AngleOp: these settings define the operation characteristic. Setting
AngleRCA is used to turn the directional characteristic, if the expected fault current
angle does not coincide with the polarizing quantity to produce the maximum torque.
The angle is positive, if operating quantity lags the polarizing quantity and negative if
it leads the polarizing quantity. The setting AngleOp (max. 180 degrees) defines the
Default
Description
Forward
Operation mode of directionality NonDir /
Forw / Rev
40.00
Positive sequence reactance reach
5.00
Positive seq. resistance for zone
characteristic angle
120.00
Zero sequence reactance reach
15.00
Zero seq. resistance for zone characteristic
angle
100.00
Fault resistance reach in ohm/loop, Ph-G
Enabled
Operation mode Disable/ Enable of Zone
timer, Ph-G
0.000
Time delay of trip, Ph-G
20
Minimum pickup phase current for Phase-to-
ground loops
IEC 61850
IEC 60617
identification
identification
ZDARDIR
S00346 V1 EN
1MRK504116-UUS C
ANSI/IEEE C37.2
device number
-
Application manual