Table 217:
CMMXU Non group settings (basic)
Name
Values (Range)
IA_DbRepInt
1 - 300
Operation
Disabled
Enabled
IBase
1 - 99999
IA_Max
0.000 -
10000000000.000
IA_RepTyp
Cyclic
Dead band
Int deadband
IA_AngDbRepInt
1 - 300
IB_DbRepInt
1 - 300
IB_Max
0.000 -
10000000000.000
IB_RepTyp
Cyclic
Dead band
Int deadband
IB_AngDbRepInt
1 - 300
IC_DbRepInt
1 - 300
IC_Max
0.000 -
10000000000.000
IC_RepTyp
Cyclic
Dead band
Int deadband
IC_AngDbRepInt
1 - 300
Table 218:
CMMXU Non group settings (advanced)
Name
Values (Range)
IA_ZeroDb
0 - 100000
IA_HiHiLim
0.000 -
10000000000.000
IA_HiLim
0.000 -
10000000000.000
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
Table continues on next page
Application manual
Unit
Step
Default
Type
1
10
-
-
Disabled
A
1
3000
A
0.001
1000.000
-
-
Cyclic
Type
1
10
Type
1
10
A
0.001
1000.000
-
-
Cyclic
Type
1
10
Type
1
10
A
0.001
1000.000
-
-
Cyclic
Type
1
10
Unit
Step
Default
m%
1
0
A
0.001
900.000
A
0.001
800.000
%
0.001
0.000
%
0.001
0.000
IED application
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Disbled/Enabled operation
Base setting for current level in A
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Description
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Magnitude factor to calibrate current at 5% of
In
Magnitude factor to calibrate current at 30%
of In