ABB RET670 Applications Manual page 127

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
Name
Values (Range)
IdUnre
1.00 - 50.00
CrossBlockEn
Disabled
Enabled
NegSeqDiffEn
Disabled
Enabled
IMinNegSeq
0.02 - 0.20
NegSeqROA
30.0 - 120.0
Table 37:
T2WPDIF (87T) Group settings (advanced)
Name
Values (Range)
EndSection1
0.20 - 1.50
EndSection2
1.00 - 10.00
SlopeSection2
10.0 - 50.0
SlopeSection3
30.0 - 100.0
I2/I1Ratio
5.0 - 100.0
I5/I1Ratio
5.0 - 100.0
OpenCTEnable
Disabled
Enabled
tOCTAlarmDelay
0.100 - 10.000
tOCTResetDelay
0.100 - 10.000
tOCTUnrstDelay
0.10 - 6000.00
Table 38:
T2WPDIF (87T) Non group settings (basic)
Name
Values (Range)
RatedVoltageW1
0.05 - 2000.00
RatedVoltageW2
0.05 - 2000.00
RatedCurrentW1
1 - 99999
RatedCurrentW2
1 - 99999
Table continues on next page
Application manual
Unit
Step
Default
IB
0.01
10.00
-
-
Enabled
-
-
Enabled
IB
0.01
0.04
Deg
0.1
60.0
Unit
Step
Default
IB
0.01
1.25
IB
0.01
3.00
%
0.1
40.0
%
0.1
80.0
%
0.1
15.0
%
0.1
25.0
-
-
Disabled
s
0.001
3.000
s
0.001
0.250
s
0.01
10.00
Unit
Step
Default
kV
0.05
400.00
kV
0.05
231.00
A
1
577
A
1
1000
IED application
Description
Unrestrained protection limit, multiple of
Winding 1 rated current
Operation Off/On for cross-block logic
between phases
Operation Off/On for neg. seq. differential
protections
Negative sequence current must be higher
than this level to be used
Operate Angle for internal / external negative
sequence fault discriminator
Description
End of section 1, multiple of Winding 1 rated
current
End of section 2, multiple of Winding 1 rated
current
Slope in section 2 of operate-restrain
characteristic, in %
Slope in section 3 of operate-restrain
characteristic, in %
Max. ratio of second harmonic to fundamental
harm dif. curr. in %
Max. ratio of fifth harmonic to fundamental
harm dif. curr. in %
Open CT detection feature. Open CTEnable
Off/On
Open CT: time in s to alarm after an open CT
is detected
Reset delay in s. After delay, diff. function is
activated
Unrestrained diff. protection blocked after this
delay, in s
Description
Rated voltage of transformer winding 1 (HV
winding) in kV
Rated voltage of transformer winding 2 in kV
Rated current of transformer winding 1 (HV
winding) in A
Rated current of transformer winding 2 in A
Section 3
121