1MRK504116-UUS C
Application manual
L1
L2
L3
(A)
(B)
(C)
CT 1500/5
Star/Wye
Connected
Protected Object
L1
L2
L3
(A)
(B)
(C)
ANSI09000170 V2 EN
Figure 39:
CT connections for restricted earth fault protection
Pos
Description
1
Scheme grounding point
Note that it is of outmost importance to insure that only one grounding point
exist in such scheme.
2
One-phase plate with stabilizing resistor and metrosil.
3
Necessary connection for the metrosil. Shown connections are applicable for both types of one-
phase plate.
4
Position of optional test switch for secondary injection into the high impedance differential IED.
5
Necessary connection for stabilizing resistor. Shown connections are applicable for both types of one-
phase plate.
6
How to connect REFPDIF (87N) high impedance scheme to one CT input in IED.