Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
3.6.5.3
Table 64:
ZMMPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
Vbase
0.05 - 2000.00
OperationDir
Disabled
Non-directional
Forward
Reverse
X1
0.50 - 3000.00
R1
0.10 - 1000.00
X0
0.50 - 9000.00
R0
0.50 - 3000.00
RFPG
1.00 - 9000.00
Timer tPG
Disabled
Enabled
tPG
0.000 - 60.000
IMinPUPG
10 - 30
IMinOpIR
5 - 30
Table 65:
ZMMAPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
Vbase
0.05 - 2000.00
Table continues on next page
Application manual
Setting of timers for distance protection zones
The required time delays for different distance-protection zones are independent of
each other. Distance protection zone1 can also have a time delay, if so required for
selectivity reasons. One can set the time delays for all zones (basic and optional) in a
range of 0 to 60 seconds. The tripping function of each particular zone can be inhibited
by setting the corresponding Operation parameter to Off. Different time delays are
possible for the ph-E (tPE) measuring loops in each distance protection zone
separately, to further increase the total flexibility of a distance protection.

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
-
-
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/l
0.01
-
-
s
0.001
%IB
1
%IB
1
Unit
Step
-
-
A
1
kV
0.05
Default
Description
Enabled
Disable/Enable Operation
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
Forward
Operation mode of directionality NonDir /
Forw / Rev
30.00
Positive sequence reactance reach
5.00
Positive seq. resistance for zone
characteristic angle
100.00
Zero sequence reactance reach
15.00
Zero seq. resistance for zone characteristic
angle
100.00
Fault resistance reach in ohm/loop, Ph-G
Enabled
Operation mode Disable/ Enable of Zone
timer, Ph-G
0.000
Time delay of trip, Ph-G
20
Minimum pickup phase current for Phase-to-
ground loops
5
Minimum operate residual current for Phase-
Ground loops
Default
Description
Enabled
Disable/Enable Operation
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
Section 3
IED application
305