1MRK504116-UUS C
Application manual
The IED has a built in function which shapes the characteristic according to the right
figure of figure 49. The load encroachment algorithm will increase the possibility to
detect high fault resistances, especially for phase-to-ground faults at remote line end.
For example, for a given setting of the load angle LdAngle for Phase selection with
load encroachment, quadrilateral characteristic function (FDPSPDIS, 21), the resistive
blinder for the zone measurement can be expanded according to the figure
higher fault resistance coverage without risk for unwanted operation due to load
encroachment. This is valid in both directions.
The use of the load encroachment feature is essential for long heavily loaded lines,
where there might be a conflict between the necessary emergency load transfer and
necessary sensitivity of the distance protection. The function can also preferably be
used on heavy loaded medium long lines. For short lines, the major concern is to get
sufficient fault resistance coverage. Load encroachment is not a major problem. So, for
short lines, the load encroachment function could preferably be switched off. See
section
"Load impedance limitation, without load encroachment
The settings of the parameters for load encroachment are done in FDPSPDIS (21)
function.
X
Zm
Load impedance area in
ANSI05000495 V2 EN
Figure 49:
Load encroachment phenomena and shaped load encroachment
characteristic defined in Phase selection with load encroachment
function FDPSPDIS (21)
Short line application
Transmission line lengths for protection application purposes are classified as short,
medium and long. The definition of short, medium and long lines is found in IEEE Std
C37.113-1999. ). The length classification is defined by the ratio of the source
impedance at the protected line's terminal to the protected line's impedance (SIR).
SIR's of about 4 or greater generally define a short line. Medium lines are those with
SIR's greater than 0.5 and less than 4
forward direction
LdAngle
R
LdAngle
Section 3
IED application
49
function".
Zm
ZL
LdAngle
LdAngle
RLdFwd
RldRev
ANSI05000495_2_en.vsd
given
R
165