Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
4.2.5.3
Table 238:
MVGGIO Non group settings (basic)
Name
Values (Range)
MV db
1 - 300
MV zeroDb
0 - 100000
MV hhLim
-10000000000.000
- 10000000000.000
MV hLim
-10000000000.000
- 10000000000.000
MV lLim
-10000000000.000
- 10000000000.000
MV llLim
-10000000000.000
- 10000000000.000
MV min
-10000000000.000
- 10000000000.000
MV max
-10000000000.000
- 10000000000.000
MV dbType
Cyclic
Dead band
Int deadband
MV limHys
0.000 - 100.000
4.2.6
4.2.6.1
Application manual

Setting parameters

Unit
Step
Type
1
m%
1
-
0.001
-
0.001
-
0.001
-
0.001
-
0.001
-
0.001
-
-
%
0.001
IEC 61850-8-1 redundant station bus communication
Function description
Parallel Redundancy Protocol Status
Duo driver configuration
Application
Parallel redundancy protocol status (PRPSTATUS) together with Duo driver
configuration (DUODRV) are used to supervise and assure redundant Ethernet
communication over two channels. This will secure data transfer even though one
communication channel might not be available for some reason. Together
PRPSTATUS and DUODRV provide redundant communication over station bus
running IEC 61850-8-1 protocol. The redundant communication use both port AB and
CD on OEM module.
Station communication
Default
Description
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping in 0.001% of range
90.000
High High limit
80.000
High limit
-80.000
Low limit
-90.000
Low Low limit
-100.000
Minimum value
100.000
Maximum value
Dead band
Reporting type
5.000
Hysteresis value in % of range (common for
all limits)
IEC 61850
IEC 60617
identification
identification
PRPSTATUS
-
DUODRV
-
Section 4
ANSI/IEEE C37.2
device number
-
-
813