Section 3
IED application
Name
Values (Range)
tPG
0.000 - 60.000
IMinPUPP
10 - 1000
IMinPUPG
10 - 1000
IMinOpIR
5 - 1000
Table 50:
ZMQAPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
Vbase
0.05 - 2000.00
OperationDir
Disabled
Non-directional
Forward
Reverse
X1
0.10 - 3000.00
R1
0.01 - 1000.00
X0
0.10 - 9000.00
R0
0.01 - 3000.00
RFPP
0.10 - 3000.00
RFPG
0.10 - 9000.00
OperationPP
Disabled
Enabled
Timer tPP
Disabled
Enabled
tPP
0.000 - 60.000
OperationPG
Disabled
Enabled
Timer tPG
Disabled
Enabled
tPG
0.000 - 60.000
IMinPUPP
10 - 1000
IMinPUPG
10 - 1000
188
Unit
Step
Default
s
0.001
0.000
%IB
1
20
%IB
1
20
%IB
1
5
Unit
Step
Default
-
-
Enabled
A
1
3000
kV
0.05
400.00
-
-
Forward
ohm/p
0.01
40.00
ohm/p
0.01
5.00
ohm/p
0.01
120.00
ohm/p
0.01
15.00
ohm/l
0.01
30.00
ohm/l
0.01
100.00
-
-
Enabled
-
-
Enabled
s
0.001
0.000
-
-
Enabled
-
-
Enabled
s
0.001
0.000
%IB
1
20
%IB
1
20
1MRK504116-UUS C
Description
Time delay of trip, Ph-G
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Minimum pickup phase current for Phase-to-
ground loops
Minimum operate residual current for Phase-
Ground loops
Description
Disable/Enable Operation
Base current, i.e. rated current
Base voltage, i.e. rated voltage
Operation mode of directionality NonDir /
Forw / Rev
Positive sequence reactance reach
Positive seq. resistance for zone
characteristic angle
Zero sequence reactance reach
Zero seq. resistance for zone characteristic
angle
Fault resistance reach in ohm/loop, Ph-Ph
Fault resistance reach in ohm/loop, Ph-G
Operation mode Disable/Enable of Phase-
Phase loops
Operation mode Disable/Enable of Zone
timer, Ph-Ph
Time delay of trip, Ph-Ph
Operation mode Disable/Enable of Phase-
Ground loops
Operation mode Disable/ Enable of Zone
timer, Ph-G
Time delay of trip, Ph-G
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Minimum pickup phase current for Phase-to-
ground loops
Application manual