Figure 274:
Switchyard layout double circuit breaker
Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE (3) is the connection from the line to the circuit breaker parts that are
connected to the busbars. DB_BUS_A (3) and DB_BUS_B (3) are the connections
from the line to the busbars.
For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE and
DB_BUS_B must be used.
Configuration setting
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
989_OP = 1
989_CL = 0
989G_OP = 1
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open
state, specify the state of the voltage supervision:
IED application
WA1 (A)
WA2 (B)
289
489G
DB_BUS_B
252
589G
6289
389G
DB_LINE
en04000518_ansi.vsd