Section 4
Station communication
838
Function block with defined functions for autorecloser indications in monitor direction,
I103AR. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each output signal.
Measurands
The measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to the
standard.
Measurands in public range
Function block that reports all valid measuring types depending on connected signals,
I103Meas.
Measurands in private range
Function blocks with user defined input measurands in monitor direction,
I103MeasUsr. These function blocks include the FUNCTION TYPE parameter for
each block in the private range, and the INFORMATION NUMBER parameter for
each block.
Fault location
The fault location is expressed in reactive ohms. In relation to the line length in
reactive ohms, it gives the distance to the fault in percent. The data is available and
reported when the fault locator function is included in the IED.
Disturbance recordings
The transfer functionality is based on the Disturbance recorder function. The
analog and binary signals recorded will be reported to the master by polling. The
eight last disturbances that are recorded are available for transfer to the master. A
file that has been transferred and acknowledged by the master cannot be
transferred again.
The binary signals that are reported by polling are those that are connected to the
disturbance function blocks B1RBDR to B6RBDR. These function blocks include
the function type and the information number for each signal. For more
information on the description of the Disturbance report in the Technical reference
manual. The analog channels, that are reported, are those connected to the
disturbance function blocks A1RADR to A4RADR. The eight first ones belong to
the public range and the remaining ones to the private range.
Settings
Settings from the local HMI
SPA, IEC 60870-5-103 and DNP3 uses the same rear communication port. Set the
parameter Operation, under Main menu/Settings /General settings /Communication /
1MRK504116-UUS C
Application manual