ABB RET670 Applications Manual page 705

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
Name
Values (Range)
Vset
85.0 - 120.0
VDeadband
0.2 - 9.0
VDeadbandInner
0.1 - 9.0
Vmax
80 - 180
Vmin
70 - 120
Vblock
50 - 120
t1Use
Constant
Inverse
t1
3 - 1000
t2Use
Constant
Inverse
t2
1 - 1000
t_MinTripDelay
3 - 120
OperationLDC
Disabled
Enabled
OperCapaLDC
Disabled
Enabled
Rline
0.00 - 150.00
Xline
-150.00 - 150.00
LVAConst1
-20.0 - 20.0
LVAConst2
-20.0 - 20.0
LVAConst3
-20.0 - 20.0
LVAConst4
-20.0 - 20.0
VRAuto
-20.0 - 20.0
OperationRA
Disabled
Enabled
tRevAct
30 - 6000
RevActLim
0 - 100
Iblock
0 - 250
HourHuntDetect
0 - 30
DayHuntDetect
0 - 100
tWindowHunt
1 - 120
NoOpWindow
3 - 30
Table continues on next page
Application manual
Unit
Step
Default
%VB
0.1
100.0
%VB
0.1
1.2
%VB
0.1
0.9
%VB
1
105
%VB
1
80
%VB
1
80
-
-
Constant
s
1
60
-
-
Constant
s
1
15
s
1
5
-
-
Disabled
-
-
Disabled
ohm
0.01
0.0
ohm
0.01
0.0
%VB
0.1
0.0
%VB
0.1
0.0
%VB
0.1
0.0
%VB
0.1
0.0
%VB
0.1
0.0
-
-
Disabled
s
1
60
%IB1
1
95
%IB1
1
150
Op/H
1
30
Op/D
1
100
Min
1
60
Op/W
1
30
IED application
Description
Voltage control set voltage, % of rated voltage
Outer voltage deadband, % of rated voltage
Inner voltage deadband, % of rated voltage
Upper lim of busbar voltage, % of rated voltage
Lower lim of busbar voltage, % of rated voltage
Undervoltage block level, % of rated voltage
Activation of long inverse time delay
Time delay (long) for automatic control
commands
Activation of short inverse time delay
Time delay (short) for automatic control
commands
Minimum operating time in inverse mode
Operation line voltage drop compensation
LDC compensation for capacitive load
Line resistance, primary values, in ohm
Line reactance, primary values, in ohm
Constant 1 for LVA, % of regulated voltage
Constant 2 for LVA, % of regulated voltage
Constant 3 for LVA, % of regulated voltage
Constant 4 for LVA, % of regulated voltage
Load voltage auto correction, % of rated
voltage
Enable block from reverse action supervision
Duration time for the reverse action block
signal
Current limit for reverse action block in % of
I1Base
Overcurrent block level, % of rated current
Level for number of counted raise/lower
within one hour
Level for number of counted raise/lower
within 24 hour
Time window for hunting alarm, minutes
Hunting detection alarm, max operations/
window
Section 3
699