Section 3
IED application
40
It shall be noted that depending on national standard and utility practices, the rated
secondary current of a CT has typically one of the following values:
1A
5A
However in some cases the following rated secondary currents are used as well:
2A
10A
The IED fully supports all of these rated secondary values.
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs with
1A and 2A secondary rating
use 5A rated CT input into the IED in order to connect CTs with
5A and 10A secondary rating
Example on how to connect a wye connected three-phase CT set to the
IED
Figure
8
gives an example about the wiring of a wye connected three-phase CT set to
the IED. It gives also an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the IED
as well.
For correct terminal designations, see the connection diagrams valid for
the delivered IED.
1MRK504116-UUS C
Application manual