ABB RET670 Applications Manual page 620

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
Name
Values (Range)
tSynchronizing
0.00 - 600.00
tExecutionFB
0.00 - 600.00
tPoleDiscord
0.000 - 60.000
Table 152:
SXCBR Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SuppressMidPos
Disabled
Enabled
Table 153:
SXSWI Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
SuppressMidPos
Disabled
Enabled
614
Unit
Step
Default
s
0.01
0.00
s
0.01
30.00
s
0.001
2.000
Unit
Step
Default
s
0.001
0.100
s
0.001
0.150
-
-
Not adaptive
s
0.001
0.200
s
0.001
0.200
-
-
Enabled
Unit
Step
Default
s
0.001
3.000
s
0.001
15.000
-
-
Not adaptive
s
0.001
0.200
s
0.001
0.200
-
-
Disconnector
-
-
Enabled
1MRK504116-UUS C
Description
Supervision time to get the signal
synchronizing in progress
Maximum time from command execution to
termination
Allowed time to have discrepancy between
the poles
Description
Supervision time for the apparatus to move
after a command
Allowed time for intermediate position
Output resets when a new correct end
position is reached
Output pulse length for open command
Output pulse length for close command
Mid-position is suppressed during the time
tIntermediate
Description
Supervision time for the apparatus to move
after a command
Allowed time for intermediate position
Output resets when a new correct end
position is reached
Output pulse length for open command
Output pulse length for close command
1=LoadBreak,2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw
Mid-position is suppressed during the time
tIntermediate
Application manual