This equation is applicable only when the loop characteristic angle for the single phase-
to-ground faults is more than three times as large as the maximum expected load-
impedance angle. For the case when the loop characteristic angle is less than three
times the load-impedance angle, more accurate calculations are necessary according to
equation 93.
é
£
×
×
RFPE
0.8
Z
ê
ë
load
min
EQUATION578 V3 EN
Where:
ϑ
is a maximum load-impedance angle, related to the maximum load power.
To avoid load encroachment for the phase-to-phase measuring elements, the set
resistive reach of any distance protection zone must be less than 160% of the minimum
load impedance.
£
×
RFPP
1.6 Z
load
EQUATION579 V2 EN
RFP
Equation
94
is applicable only when the loop characteristic angle for the phase-to-
phase faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to equation 95.
é
× ê
£
×
RFPP 1.6 Z
cos
load min
ë
IECEQUATION2307 V1 EN
All this is applicable for all measuring zones when no Power swing detection function
ZMRPSB (78) is activated in the IED. Use an additional safety margin of
approximately 20% in cases when a ZMRPSB (78) function is activated in the IED,
refer to the description of Power swing detection function ZMRPSB (78).
×
+