Setting Guidelines - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
3.12.2.3
Application manual
ZMQPDIS
(Distance)
QCBAY
Operator place
(Bay control)
Res. granted
QCRSV
(Reservation)
Close CB
SMBRREC
(Auto-
reclosure)
Open rel.
Interlocking
Close rel.
function
Open rel.
block
Close rel.
(Not a LN)
Position
GAPC
(Generic
Automatic
Open/Close
Process
Control)
Open/Close
ANSI05000120 V1 EN
Figure 237:
Example overview of the interactions between functions in a typical bay

Setting guidelines

The setting parameters for the apparatus control function are set via the local HMI or
PCM600.
SMPPTRC
SECRSYN
(Trip logic)
(Synchrocheck)
Synchrocheck
OK
selection
Res. req.
SCSWI
(Switching control)
Res. req.
SCILO
(Interlocking)
SCILO
(Interlocking)
Enable
Enable
open
close
Res.
granted
SCSWI
(Switching control)
Section 3
IED application
Trip
Open cmd
Close cmd
SXCBR
(Circuit breaker)
Position
I/O
Open cmd
Close cmd
SXSWI
(Disconnector)
Position
I/O
en05000120_ansi.vsd
611