Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
3.6.2.3
Table 53:
ZMCPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
OperationDir
Disabled
Non-directional
Forward
Reverse
OperationPP
Disabled
Enabled
X1FwPP
0.10 - 3000.00
R1PP
0.01 - 1000.00
RFltFwdPP
0.10 - 3000.00
X1RvPP
0.10 - 3000.00
RFltRevPP
0.10 - 3000.00
Timer tPP
Disabled
Enabled
tPP
0.000 - 60.000
OperationPG
Disabled
Enabled
X1FwPG
0.10 - 3000.00
Table continues on next page
248
Setting of timers for distance protection zones
The required time delays for different distance-protection zones are independent of
each other. Distance protection zone1 can also have a time delay, if so required for
selectivity reasons. One can set the time delays for all zones (basic and optional) in a
range of 0 to 60 seconds. The tripping function of each particular zone can be inhibited
by setting the corresponding Operation parameter to Disabled. Different time delays
are possible for the ph-E (tPG) and for the ph-ph (tPP) measuring loops in each
distance protection zone separately, to further increase the total flexibility of a distance
protection.

Setting parameters

Settings for ZMCPDIS (21) are valid for zone 1, while settings for
ZMCAPDIS (21) are valid for zone 2 - 5
Unit
Step
-
-
A
1
kV
0.05
-
-
-
-
ohm/p
0.01
ohm/p
0.01
ohm/l
0.01
ohm/p
0.01
ohm/l
0.01
-
-
s
0.001
-
-
ohm/p
0.01
Default
Description
Enabled
Disable/Enable Operation
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
Forward
Operation mode of directionality NonDir /
Forw / Rev
Enabled
Operation mode Disable/Enable of Phase-
Phase loops
30.00
Positive sequence reactance reach, Ph-Ph,
forward
5.00
Positive seq. resistance for characteristic
angle, Ph-Ph
30.00
Fault resistance reach, Ph-Ph, forward
30.00
Positive sequence reactance reach, Ph-Ph,
reverse
30.00
Fault resistance reach, Ph-Ph, reverse
Enabled
Operation mode Disable/Enable of Zone
timer, Ph-Ph
0.000
Time delay of trip, Ph-Ph
Enabled
Operation mode Disable/Enable of Phase-
Ground loops
30.00
Positive sequence reactance reach, Ph-G,
forward
1MRK504116-UUS C
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents