Section 3
IED application
404
2ndHarmStab: Operate level of 2nd harmonic current restrain set in % of the
fundamental current. The setting range is 5 - 100% in steps of 1%. Default setting is 20%.
ANSI09000636 V1 EN
Figure 183:
Directional function characteristic
1. RCA = Relay characteristic angle
2. ROA = Relay operating angle
3. Reverse
4. Forward
Settings for each step
x means step 1, 2, 3 and 4.
3
1
2
2
4
I
1MRK504116-UUS C
V
ref
dir
ANSI09000636-1-en.vsd
Application manual