ABB RET670 Applications Manual page 174

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
168
From an application point of view there exists three types of network configurations
(classes) that must be considered when making the settings for the protection function.
The different network configuration classes are:
1.
Parallel line with common positive and zero sequence network
2.
Parallel circuits with common positive but isolated zero sequence network
3.
Parallel circuits with positive and zero sequence sources isolated.
One example of class 3 networks could be the mutual coupling between a 400kV line
and rail road overhead lines. This type of mutual coupling is not so common although
it exists and is not treated any further in this manual.
For each type of network class, there are three different topologies; the parallel line can
be in service, out of service, out of service and grounded in both ends.
The reach of the distance protection zone 1 will be different depending on the
operation condition of the parallel line. This can be handled by the use of different
setting groups for handling the cases when the parallel line is in operation and out of
service and grounded at both ends.
The distance protection within the IED can compensate for the influence of a zero
sequence mutual coupling on the measurement at single phase-to-ground faults in the
following ways, by using:
The possibility of different setting values that influence the ground-return
compensation for different distance zones within the same group of setting
parameters.
Different groups of setting parameters for different operating conditions of a
protected multi circuit line.
Most multi circuit lines have two parallel operating circuits.
Parallel line applications
This type of networks is defined as those networks where the parallel transmission
lines terminate at common nodes at both ends.
The three most common operation modes are:
1.
Parallel line in service.
2.
Parallel line out of service and grounded.
3.
Parallel line out of service and not grounded.
1MRK504116-UUS C
Application manual